NESCOM

The type-tested medium-voltage switchgear with withdrawable unit technology is distinguished by its high performance data but with a very compact design. Modern switchgear offers innovative detailed solutions, high functionality and safety.

Pressure relief channels are used to discharge hot gases arising in the event of an internal arc.

Design features and classification under standard IEC 62271-200

Busbar system Single
Operational availability category LSC 2B
Partition class PM
Internal arc resistance classification IAC AFLR

Switchgear system

up to 17.5 kV

 

Rated values

max.

 

Rated voltage  

17.5

kV

Rated power-frequency withstand voltage

38

kV

Rated lightning impulse withstand voltage

95

kV

Rated busbar current

2,000

A

Rated short-time withstand current

31.5

kA

Rated impulse current

80

kA

Rated short circuit period

3

s

Internal arc resistance classification 

AFLR 31,5 kA / 1 s